182
182
NC2 0 - Manual - 01 - 2015
APPENDIX
Residual overcurrent 50N/51N - Moderately inverse time curve (ANSI/IEEE type MI)
F_51N-ANSIMI-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
EC
/I
E
>inv
0.01
0.1
1
10
100
1000
10000
t [s]
t
E
>
inv
= 10 s
t
E
>
inv
= 60 s
t
E
>
inv
= 5 s
t
E
>
inv
= 1 s
t
E
>
inv
= 0.02 s
t
E
>
inv
= 0.2 s
t
E
>
inv
= 0.1 s
t
E
>
inv
= 0.5 s
t =
t
E
>
inv
·
[(I
EC
/I
E
>
inv
)
0.02
-1]
0.01
+ 0.023
Note: match of operating and setting time takes place when I
EC
/I
E
>
inv
= 1.664