APPENDIX
198
198
NC2 0 - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
IN>AL Start LEDs IN>ALST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IN>AL Trip LEDs IN>ALTR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46N Alarm threshold defi nite time
State
OFF | ON
Pickup value
INn 0.01 ... 1.00 step = 0.01
IN>ALdef within CLP INCLP>ALdef INn 0.01 ... 1.00 step = 0.01
IN>ALdef Operating time
Value
s
0.04 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 500 step = 1
IN> Element
Setpoints
IN> Enable IN> Enable
OFF | ON
IN> Curve type IN>Curve
IEC/BS A | IEC/BS B | IEC/BS C | ANSI/IEEE MI |
ANSI/IEEE VI | ANSI/IEEE EI | DEFINITE
INCLP> Mode INCLP> Mode
OFF | ON - Element blocking | ON - Change setting
INCLP> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN> Logical block IN>BLK1
OFF | ON
IN> Input selective block IN>BLK2IN
OFF | ON
IN> Output selective block IN>BLK2OUT
OFF | ON
IN> Breaker failure IN>BF
OFF | ON
IN>AL Disabling by IN> IN>ALdisbyIN>
OFF | ON
IN> Start relays IN>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN> Trip relays IN>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN> Start LEDs IN>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IN> Trip LEDs IN>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46N First threshold defi nite time
State
OFF | ON
Pickup value
INn 0.01 ... 2.00 step = 0.01
IN>def within CLP INCLP>def INn 0.01 ... 2.00 step = 0.01
IN>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 50.0 step = 0.1
Inverse time
46N First threshold inverse time
State
OFF | ON
Pickup value
INn 0.01 ... 1.00 step = 0.01
IN>inv within CLP INCLP>inv INn 0.01 ... 1.00 step = 0.01
IN>inv Operating time tN>inv s
0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
IN>> Element
Setpoints
IN>> Enable IN>> Enable
OFF | ON
INCLP>> Mode INCLP>> Mode
OFF | ON - Element blocking | ON - Change setting
INCLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN>> Logical block IN>>BLK1
OFF | ON
IN>> Input selective block IN>>BLK2IN
OFF | ON