Fuel Tank Leak, AC Fail, Low Ambient Temperature, High Ambient Temperature, Low Suction Pressure, Water
Reservoir Empty, High Water Level or Water Reservoir Low.
Fail to Start
Disconnect #1, #9, #10 and #12 engine wires (See drawing for more details). Start the cranking sequence (Example:
Remove Remote Automatic Start jumper). Wait until the cranking sequence ends.
Overspeed
If your engine has an overspeed switch, switch it to the ON position. If not, disconnect #3 engine wire (See drawing
for more details) and put a jumper between #3 and #6. (Note: You don't need to start the engine to activate this
alarm.)
Electronic Control Module Selector Switch in Alternate Position (301)
Disconnect #301 engine wire. Put a jumper between #301 input and ground (See drawing for more details).
Fuel Injection Malfunction (302)
Disconnect #302 engine wire. Put a jumper between #302 input and ground (See drawing for more details).
Electronic Control Module Warning ( 303 )
Disconnect #303 engine wire. Put a jumper between #303 input and ground (See drawing for more details).
Electronic Control Module Fault ( 304 )
Disconnect #304 engine wire. Put a jumper between #304 input and ground (See drawing for more details).
Low Engine Temperature (312)
Disconnect #312 engine wire. Put a jumper between #312 input and ground (See drawing for more details).
Low Oil Pressure
Disconnect #4 engine wire (See drawing for more details). Put a jumper between #4 and ground. Start the engine.
High Engine Temperature
Disconnect #5 engine wire (See drawing for more details). Put a jumper between #5 and ground. Start the engine.
Battery 1 Failure
Disconnect #6 engine wire (See drawing for more details).
Weak Battery 1
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Weak Battery 1 setpoint to maximum allowable.
Weak Battery 2
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Weak Battery 2 setpoint to maximum allowable.
Battery 1 Overvoltage
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Overvoltage Battery 1 setpoint to minimum allowable.
Battery 2 Overvoltage
You need to be logged in to modify these settings. Press Config button (On the membrane). Go to
Config>Advanced>Factory Settings 2. Change Overvoltage Battery 2 setpoint to minimum allowable.
Battery 2 Failure
Disconnect #8 engine wire (See drawing for more details).
Loss of Continuity 1
Disconnect #9 engine wire (See drawing for more details). Wait 1-2 minutes.