Press “Pressure”.
- Verify that the pressure reading on the screen matches with the calibrated pressure gauge installed on the
sensing line.
- Choose the desired units of measurement for pressure reading.
- Adjust, if required, the range of the digital pressure gauge at Max. Pres.
- Insert the Cut-Out and Cut-In pressure values of the fire pump.
- Insert, if so desired, the Cut-Out and Cut-In pressure values of the jockey pump.
Note: The jockey pump Cut-Out and Cut-In values must be set at the jockey pump controller itself. Inserting these
values at the Fire Pump Controller is only for pressure recording data purposes.
To continue to next step, press “ ˂ First Start Up “.
Go back to the controller start-up page and press the “Other Configuration” button. Enter the time and date. Select
the “Automatic shutdown” and the duration the pump will keep running after the automatic stop if an automatic stop
is desired. Select the frequency at which the periodic test will occur, the day of the week, the hour and the duration
of the test. Also, enter the duration of the Manual Run Test.