This table allows viewing of the exact values used to generate the Power Curves with the precise time. Press the
blue button on the top left corner to return to the graph page.
This page is used to access all past log files. Each log file is a CSV file containing the time, the date, the Cut-in, the
Cut-out, the system pressure, the battery voltages and currents, the engine run signal, the jockey pump run signal
and the log event message. Each file can contain up to 1 MB of data. The month and year is integrated in the title.
At the beginning of each month, a new CSV file is created. Each time a CSV file is full, a new one is created with an
incremented number in the title. Press on the file to consult this content.