This page is used to visualize the program version, the serial number and the model of the controller.
Some parameters can be changed on this page, but be careful, modifying a parameter will change the basic
operation of the controller. Afterwards the controller may no longer respect the NFPA standard.
- Automatic Controller: Enable automatic starting causes.
- Pressure Actuated Controller: Enable the automatic controller to start following a pressure drop.
It is possible to reload a past configuration by pressing the "reload configuration" button. Dates with an "*" are
settings following a "Service".
Do not change a parameter on this page without previously consulting a Tornatech representant.
This page is used to configure the Lockout input and the Interlock output parameters. To be active those options
need to be assigned to an Input or an Output on the IO board.
Lockout is an Input that disables the engine from starting.
-Shutdown Engine: If enabled, the lockout signal will also act as a shutdown and will stop the engine if it is running.
-Enable in Manual: If checked, activation of the lockout input will prevent the Manual start.
-Enable in Automatic: If checked, activation of the lockout input will prevent the Automatic start.