Run Period Timer
This timer sets the time the engine will keep running after the demand is resolved.
Time Range: 1-1440 Minutes
Most alarms are not configurable in the field, but some are with the appropriate password level. If it's configurable,
the checkboxes will be in white. Otherwise the checkboxes will be grey. Also, the two last fields: Value Usage and
Analog Value are not always visible.
Start Test: The alarm can be tested using this button. This test will only announce the chosen alarm. It will activate
the bell if the alarm is audible and will activate any output relays associated with this alarm. The test will not activate
other common alarms or other components. To stop the testing, press the “Stop Test” button.
Enable: Check this box to enable the Alarm/Warning.
Alarm: Makes this signal an alarm (red display). Otherwise, it will be a warning (yellow display).
Audible: Check this box to make the bell ring while this alarm is active.