76
4400 Series Installation and Operation Manual – 64527-008
12.4 Touch Screen Display
The various components of the touchscreen display are identied in Figure 12-3.
2
3
1
3a
3b
4
5
4400F3F300FAB 30KVA
2014012345
Touchscreen Layout
No. Function
1 Quick Access Toolbar – Interface/Status Switches (push-button icon changes to reect
current status) (See Section 12.5)
2 Header Bar – Displays system load, status, and time.
3 Menu TABS – Top level menu. Touch a Tab to activate the display mode
3a Data display area
3b Update – Displays current status and operation hints.
4 Footer Bar – Displays Faults, Warnings, and UPS Operating Mode.
5 UPS Control – Toggles between On-Line (RUN) and bypass (STOP) modes. (See Sec-
tion 12.13)
Press Run: UPS switches to On-Line mode, label changes to STOP.
Press STOP: UPS switches to Bypass mode, label changes to RUN.
FIGURE 12.3: TOUCHSCREEN DISPLAY COMPONENTS (INITIAL MAIN DISPLAY)