Register Function / Title Bank Mask Adjustment Range Multiplier
34
BASE FREQUENCY #2
0 / 1 FFFF
09C4 9C40 (25.00 400.00)
0.01
35
MAXIMUM OUTPUT
VOLTAGE #2
0 / 1 FFFF
0000 0258 (0 600)
1
36
VOLTAGE BOOST #2
0 / 1 FFFF
0000 012C (0.0 30.0)
0.1
37
ELECTRONIC THERMAL
PROTECT LVL #2
0 / 1 00FF
000A 0064 (10 100)
1
38
STALL PROTECTION
SELECTION #2
0 / 1 0040 0000: ON (0)
0040: OFF (1)
39 0
STALL PROTECTION
LEVEL #2
0 / 1 00FF
000A 00D7 (10 215)
1
3A
ACCELERATION TIME #2
0 / 1 FFFF
0001 EA60 (0.1~ 6000.0)
0001 EA60 (0.01~ 600.00)
0.1
0.01
3B
DECELERATION TIME #2
0 / 1 FFFF
0001 EA60 (0.1~ 6000.0)
0001 EA60 (0.01~ 600.00)
0.1
0.01
3C
ACC/DEC PATTERN #2
SELECTION
0 / 1 0030 0000: Linear (0)
0010: Self-adjusting (1)
0020: S-Pattern #1 (2)
0030: S-Pattern #2 (3)
3D
ACC/DEC #1/#2 SWITCH
FREQUENCY
0 / 1 FFFF
0000 Fmax
0.01
11.2.3
11.2.311.2.3
11.2.3
GROUP:PANEL CONTROL PARAMETERS
GROUP:PANEL CONTROL PARAMETERSGROUP:PANEL CONTROL PARAMETERS
GROUP:PANEL CONTROL PARAMETERS
Register Function / Title Bank Mask Adjustment Range Multiplier
3E
DIRECTION SELECTION
(FORWARD/REV)
0 / 1 0004 0000: Reverse (0)
0004: Forward (1)
3F
STOP PATTERN
SELECTION
0 / 1 0040 0000: Decelerated stop (0)
0040: Coast stop (1)
40
FUNDAMENTAL PARAM
SWITCHING
0 / 1 0004 0000: V/F #1 (1)
0004: V/F #2 (2)
41
ACCEL/DECEL #1/#2
SELECTION
0 / 1 0008 0000: Acc / dec #1 (1)
0008: Acc / dec #2 (2)
42
PANEL RESET SELECTION
0 / 1 0030 0000: All possible (0)
0010: OL only (1)
0020: OL, OC only (2)
43
PANEL FEEDBACK
CONTROL
0 / 1 0001 0000: Feedback valid (0)
0001: Feedback invalid (1)