162 ACE-tronics G9 ASD Installation and Operation Manual
Dynamic Braking Torque Limit 3 Level
Program To r que Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #3 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number F447
Parameter Type — Numerical
Factory Default 250.0 (Disabled)
Changeable During RunYes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 4 Level
Program To r que Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #4 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number F448
Parameter Type — Numerical
Factory Default 250.0 (Disabled)
Changeable During RunYes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Dynamic Braking Torque Limit 4 Level
Program To r que Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #4 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Direct Access Number F449
Parameter Type — Numerical
Factory Default 250.0 (Disabled)
Changeable During RunYes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Accel/Decel Operation After Torque Limit
Program To r que Torque Limit
In a Crane/Hoist application that is operating using a mechanical brake, this
parameter is used to minimize the delay between the brake release and the
output torque reaching a level that can sustain the load.
This setting may reference time or the operating speed of the motor.
Settings:
In Sync with Accel/Decel
In Sync with Minimum Time
Direct Access Number F451
Parameter Type — Selection List
Factory Default In Sync with Accel/
Decel
Changeable During RunYes
Power Running Stall Continuous Trip Detection Time
Program Protection Stall
This parameter is used to extend the Over-Voltage Stall (F305) and the Over-
Current Stall (F017) time settings.
Direct Access Number F452
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run Yes
Minimum — 0.0
Maximum — 1.0
Units — Seconds
F447 F452