P9 ASD Installation and Operation Manual 277
Table 20. 460-Volt Chassis Standard Ratings Table.
Model
Number
VT130P9U
Typical
Motor HP
100% Output
Current
Continuous
Overload Current
120% for 60
Seconds
Input Voltage
3-Ph 50/60
±2 Hz
Output Voltage
3-Ph Variable
Frequency
4015 1.0 2.1 A 2.52 A
380 – 480 VAC
(±10%)
Input Voltage
Level (Max.)
4025 2.0 3.4 A 4.08 A
4035 3.0 4.8 A 5.76 A
4055 5.0 7.6 A 9.00 A
4080 7.5 11.0 A 13.0 A
4110 10 14.0 A 17.0 A
4160 15 21.0 A 25.0 A
4220 20 27.0 A 32.0 A
4270 25 34.0 A 41.0 A
4330 30 40.0 A 48.0 A
4400 40 52.0 A 62.0 A
4500 50 65.0 A 78.0 A
4600 60 77.0 A 92.0 A
4750 75 96.0 A 115 A
410K 100 124 A 149 A
412K 125 156 A 187 A
415K 150 180 A 216 A
420K 200 240 A 288 A
425K 250 302 A 362 A
430K 300 361 A 433 A
435K 350 414 A 497 A
440K 400 477 A 572 A

Table of Contents