Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 105
V/I Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets V/I Input Point 1 Frequency and is the fre-
quency that is associated with the setting of V/I Input Point 1 Set-
ting when operating in the Speed Control mode.
See V/I Input Point 1 Setting (F201) for additional information on
this parameter.
Direct Access Number
F202
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
V/I Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the V/I input level that is associated with V/I
Input Point 2 Frequency when operating in the Speed control
mode or is associated with the V/I Input Point 1 Rate when oper-
ating in the Torque Control mode.
This value is entered as 0% to 100% of the V/I input signal range.
See V/I Input Point 1 Setting (F201) for additional information on
this parameter when used for Speed control.
See V/I Input Point 1 Rate (F203) for additional information on
this parameter when used for Torque Control.
Direct Access Number
F203
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
V/I Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets V/I Input Point 2 Frequency and is the fre-
quency that is associated with the setting of V/I Input Point 2 Set-
ting when operating in the Speed Control mode.
See V/I Input Point 1 Setting (F201) for additional information on
this parameter.
Direct Access Number
F204
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
F202F205

Table of Contents