Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 137
Number of Times to Retry
Program Protection Retry/Restart
After a trip has occurred, this parameter sets the number of times
that an automatic system restart is attempted for a qualified trip.
The trip conditions listed below will NOT initiate the automatic
Retry/Restart function:
Input Phase Loss (Input Phase Failure)
Output Phase Loss (Output Phase Failure)
Output Current Protection Fault
Output Current Detector Error
Load Side Over-Current at Start
Earth Fault (Ground Fault)
Over-Current During Acceleration
Arm Over-Current at Start-Up
DBR Resistor Over-Current
Low-Current
Voltage Drop In Main Circuit
EEPROM Data Fault (EEPROM Fault)
Flash Memory/Gate Array/RAM-ROM Fault
CPU Fault
Emergency Off
Communication Error
Option Fault
Sink/Source Setting Error
Over-Speed Error
Over-Torque
Key Error
External Thermal Error
Externally-Controlled Interrupt
See the section titled System Setup Requirements on pg. 5 for
additional information on this setting.
Direct Access Number
F303
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 10
F303F304