Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 143
Drooping Insensitive Torque
Program Feedback Drooping Control
This parameter defines a torque range in which the Drooping
Control settings will be ignored and the programmed torque set-
tings will be followed.
Direct Access Number
F323
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Drooping Output Filter
Program Feedback Drooping Control
This parameter is used to set the rate of output change allowed
when operating in the Drooping Control mode.
Jerky operation may be reduced by increasing this setting.
Direct Access Number
F324
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 200.0
Units — RAD