Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 155
(Virtual Linear Pump) Transducer Maximum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the maximum level of the transducer
range for Virtual Linear Pump operation.
Direct Access Number
F393
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
Virtual Linear Pump Minimum (Threshold)
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the minimum setpoint within the Virtual
Linear Pump operating domain.
Direct Access Number
F394
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 10
Maximum — Virtual Linear Pump
Maximum Setting (F395)
Virtual Linear Pump Maximum (Threshold)
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the maximum setpoint within the Virtual
Linear Pump operating domain.
Direct Access Number
F395
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — Virtual Linear Pump
Minimum Setting (F394)
Maximum — 165
Virtual Linear Pump Command Source
Program Virtual Linear Pump Settings
During Direct mode or the Process Hold mode operation, this
parameter sets the Virtual Linear Pump command source.
Settings:
0 — EOI
1 — *V/I
2 — RR
3 — Communication Board
Note: *If Process Hold is selected at F390, selecting V/I here will
result in an error message.
Direct Access Number
F396
Parameter Type — Selection List
Factory Default — EOI
Changeable During Run — No
F393F397