Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 157
Slip Frequency Gain
Program Motor Vector Motor Model
This parameter provides a degree of slip compensation for a
given load. A higher setting here decreases the slip allowed for a
given load/ASD output ratio.
Direct Access Number
F401
Parameter Type — Numerical
Factory Default — 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %
Autotune 2
Program Motor Vector Motor Model
This parameter introduces a thermal element into the autotuning
equation and is used to automatically adjust the Autotune param-
eter values as a function of increases in the temperature of the
motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Direct Access Number
F402
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
(Virtual Linear Pump) Transducer Minimum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the minimum level of the transducer range
for Virtual Linear Pump operation.
Direct Access Number
F403
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7