Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 159
Motor Rated Current (Nameplate)
Program Motor Vector Motor Model
This parameter is used to set the (nameplated) current rating of
the motor being used.
Direct Access Number
F406
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 0.1
Maximum — 2000.0
Units — Amps
Motor Rated RPM (Nameplate)
Program Motor Vector Motor Model
This parameter is used to input the (nameplated) rated speed of
the motor.
Direct Access Number
F407
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 100
Maximum — 60000
Units — RPM
Base Frequency Voltage 1
Program Vector Vector Motor Model
The Motor 1 Base Frequency Voltage 1 is the Motor 1 output volt-
age at the Base Frequency (F014). Regardless of the pro-
grammed value, the output voltage cannot be higher than the
input voltage.
The actual output voltage will be influenced by the input voltage
of the ASD and the Supply Voltage Correction setting (F307).
Direct Access Number
F409
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 50.0
Maximum — (ASD-Dependent)
Units — Volts
Motor Constant 1 (Torque Boost)
Program Motor Vector Motor Model
This parameter sets the primary resistance of the motor. Increas-
ing this value can prevent a drop in the torque of the motor at low
speeds. Increasing this value excessively can result in nuisance
overload tripping.
Direct Access Number
F410
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Constant 2 (No-Load Current)
Program Motor Vector Motor Model
This parameter is used to set the current level required to excite
the motor. Specifying a value that is too high for this parameter
may result in hunting (erratic motor operation).
Direct Access Number
F411
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 10
Maximum — 90
Units — %
F406F412