Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 169
RX2 Input Gain
Program Frequency Speed Reference Setpoints
This parameter is used to fine-tune the gain of the RX2 (AI1
Option) input terminal when this terminal is used as the control
input while operating in the Speed Control mode or the Torque
Control mode.
This setting may be used to ensure that the 100% level of the
input source (pot, pressure transducer, flow meter, etc.) is also
the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and
adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number
F477
Parameter Type — Numerical
Factory Default — 128
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Option V/I Input Bias
Program Frequency Speed Reference Setpoints
This parameter is used to fine-tune the gain of the Optional AI2
input terminal when this terminal is used as the control input
while operating in the Speed Control mode or the Torque Control
mode.
This setting may be used to ensure that the 100% level of the
input source (pot, pressure transducer, flow meter, etc.) is also
the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and
adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number
F478
Parameter Type — Numerical
Factory Default — 128
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Option V/I Input Gain
Program Frequency Speed Reference Setpoints
This parameter is used to fine-tune the gain of the Optional AI2
input terminal when this terminal is used as the control input
while operating in the Speed Control mode or the Torque Control
mode.
This setting may be used to ensure that the 100% level of the
input source (pot, pressure transducer, flow meter, etc.) is also
the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and
adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number
F479
Parameter Type — Numerical
Factory Default — 128
Changeable During Run — Yes
Minimum — 0
Maximum — 255
F477F480