188 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Abnormal Speed Detection Time
Program Protection Abnormal Speed Settings
This parameter sets the time that an over-speed condition must
exist to cause a trip.
This parameter functions in conjunction with the settings of F623
and F624.
Direct Access Number —
F622
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.00
Units — Seconds
Over-Speed Detection Frequency Upper Band
Program Protection Abnormal Speed Settings
This parameter sets the upper level of the Base Frequency range
that, once exceeded, will cause an Over-Speed Detected alert.
This parameter functions in conjunction with the settings of F622
and F624.
Direct Access Number —
F623
Parameter Type — Numerical
Factory Default — 0.00 (Dis-
abled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
Maximum — (ASD-Dependent)
Units — Hz
Over-Speed Detection Frequency Lower Band
Program Protection Abnormal Speed Settings
This parameter sets the lower level of the Base Frequency range
that, once the output speed falls below this setting, will cause a
Speed Drop Detected alert.
This parameter functions in conjunction with the settings of F622
and F623.
Direct Access Number —
F624
Parameter Type — Numerical
Factory Default — 0.00 (Dis-
abled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
Maximum — (ASD-Dependent)
Units — Hz
Under-Voltage Detection Level
Program Protection Under-Voltage/Ridethrough
This parameter sets the voltage threshold level that is used
as a setpoint for under-voltage tripping.
This function is enabled at F627.
Direct Access Number —
F625
Parameter Type — Numerical
Factory Default — 60
Changeable During Run — No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — %
F622 – F626