Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Forced Fire-Speed Control
Program Protection Fire-Speed Control
This parameter is used to enable the Forced Fire Speed func-
tion. The Forced Fire Speed function runs Preset Speed 15 in the
event of an emergency. Preset Speed 15 must be configured to
use the Forced Fire Speed function.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number
F650
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Under-Torque Detection
Program Protection Under-Torque Detection
This parameter sets the ASD operating mode and disposition in
the event that an Under-Torque condition were to occur.
For an Under-Torque event to occur, the minimum criteria of
parameters F652 F655 must be met:
Settings:
0 — Alarm Mode
1 — Trip Mode
Direct Access Number
F651
Parameter Type — Selection List
Factory Default — Alarm Mode
Changeable During Run — Yes
F650F652