196 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Adding Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the
external adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature.
The selected input is used as a modifier of the programmed Out-
put Frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
5 — EOI Keypad
6 — RS485/BACnet
7 — Communication Option Board
8 — RX2 (AI1 Option)
9 — Option V/I (AI2 Option)
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
13 — Binary/BCD (Option)
Direct Access Number
F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the
external adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature.
The selected input is used as a multiplier of the commanded fre-
quency.
If Setting (A729) is selected, the % value entered at parameter
A729 is used as the multiplier of the commanded frequency.
Note: Contact the TIC Customer Support Center for more
information on using the A729 selection.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Setting (A729)
5 — RX2 (AI1 Option) Option
Direct Access Number
F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F660F669