208 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Trace Cycle
Program Utilities Trace
This parameter sets the record time for the Trace Data events
selected at F742 – F745.
See F740 for additional information on this parameter.
Settings:
0 — 4 mS
1 — 20 mS
2 — 100 mS
3 — 1 Second
4 — 10 Seconds
Direct Access Number —
F741
Parameter Type — Selection List
Factory Default — 100 mS
Changeable During Run — Yes
Trace Data 1
Program Utilities Trace
This parameter is used to select the Trace Data 1 item from
Table 13 on page 259 to be read and stored in accordance with
the setup of parameters F740 and F741.
See F740 for additional information on this parameter.
Direct Access Number —
F742
Parameter Type — Selection List
Factory Default — Output Fre-
quency
Changeable During Run — Yes
Trace Data 2
Program Utilities Trace
This parameter is used to select the Trace Data 2 item from
Table 13 on page 259 to be read and stored in accordance with
the setup of parameters F740 and F741.
See F740 for additional information on this parameter.
Direct Access Number —
F743
Parameter Type — Selection List
Factory Default — Freq. Refer-
ence
Changeable During Run — Yes
Trace Data 3
Program Utilities Trace
This parameter is used to select the Trace Data 3 item from
Table 13 on page 259 to be read and stored in accordance with
the setup of parameters F740 and F741.
See F740 for additional information on this parameter.
Direct Access Number —
F744
Parameter Type — Selection List
Factory Default — Output Cur-
rent
Changeable During Run — Yes
Trace Data 4
Direct Access Number —
F745
Program Utilities Trace
Parameter Type — Selection List
This parameter is used to select the Trace Data 4 item from
Table 13 on page 259 to be read and stored in accordance with
the setup of parameters F740 and F741.
See F740 for additional information on this parameter.
Factory Default — DC Voltage
Changeable During Run — Yes
F741 – F748