214 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Communications Time-Out Action (2- and 4-wire RS485)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications
network by determining the action to be taken in the event of a
time-out (Time-Out Action).
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Settings:
0 — No Action/No Action
1 — Alarm/No Action
2 — Trip/No Action
3 — No Action/Alarm
4 — Alarm/Alarm
5 — Trip/Alarm
6 — No Action/Trip
7 — Alarm/Trip
8 — Trip/Trip
Direct Access Number
F804
Parameter Type — Selection List
Factory Default — Trip/Trip
Changeable During Run — Yes
Send Delay Time (2-Wire RS485)
Program Communications Communication Settings
This parameter sets the RS485 (2-wire) response delay time.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Direct Access Number
F805
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F804F806