EasyManua.ls Logo

Toshiba Q9+ - Page 79

Toshiba Q9+
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BACnet Setup
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 67
BACnet
®
I/O, and Values
Table 4. BACnet
®
Binary Inputs.
Digital Input
Terminal
Binary Input
Object ID
Object
Name
Description Status Access
F
Binary Input
#6
(BI6)
F Status
Monitors the status of the F input
terminal (Forward Run Command)
On/Off R
R
Binary Input
#7
(BI7)
R Status
Monitors the status of the R input
terminal (Reverse Run Command)
On/Off R
ST
Binary Input
#8
(BI8)
ST Status
Monitors the status of the ST input
terminal (Standby Command)
On/Off R
RES
Binary Input
#9
(BI9)
RES
Status
Monitors the status of the RES
input terminal (Fault Reset
Command)
On/Off R
S1
Binary Input
#10
(BI10)
S1 Status
Monitors the status of the S1 input
terminal (Fire-speed Command)
On/Off R
S2
Binary Input
#11
(BI11)
S2 Status
Monitors the status of the S2 input
terminal (Preset Speed Bit 2)
On/Off R
S3
Binary Input
#12
(BI12)
S3 Status
Monitors the status of the S3 input
terminal (Damper Closed
Feedback)
On/Off R
S4
Binary Input
#13
(BI13)
S4 Status
Monitors the status of the S4 input
terminal (Emergency Off (NC))
On/Off R
LI5*
Binary Input
#14
(BI14)
LI5 Status
Monitors the status of the LI5
input terminal
On/Off R
LI6*
Binary Input
#15
(BI15)
LI6 Status
Monitors the status of the LI6
input terminal
On/Off R
LI7*
Binary Input
#16
(BI16)
LI7 Status
Monitors the status of the LI7
input terminal
On/Off R
* The ETB004Z expansion I/O card is required to use this input.