BACnet Setup
Q9 Plus ASD Install/Op Manual
68 https://www.toshiba.com/tic/
LI8*
Binary Input
#17
(BI17)
LI8 Status
Monitors the status of the LI8
input terminal
On/Off R
FLA/FLC
(FL)
Binary Input
#0
(BI0)
FL Status
Monitors the status of the FL
output relay (Any Fault (NC))
On/Off R
DSA/DSB
(OUT 1)
Binary Input
#1
(BI1)
OUT 1
Status
Monitors the status of the OUT 1
output relay (Open Damper
Command)
On/Off R
OUT 2
Binary Input
#2
(BI2)
OUT 2
Status
Monitors the status of the OUT 2
output relay (Acc or Dec
Complete)
On/Off R
R2*
Binary Input
#3
(BI3)
R2 Status
Monitors the status of the R2
output relay
On/Off R
OUT 5*
Binary Input
#4
(BI4)
OUT 5
Status
Monitors the status of the OUT 5
open collector output
On/Off R
OUT 6*
Binary Input
#5
(BI5)
OUT 6
Status
Monitors the status of the OUT 6
open collector output
On/Off R
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
Table 4. BACnet
®
Binary Inputs. (Cont)
Digital Input
Terminal
Binary Input
Object ID
Object
Name
Description Status Access
Table 5. BACnet
®
Binary Values.
Binary Value
Object ID
Object Name Description Status Access
Binary Value
#0 (BV0)
Run/Stop
Status
Indicates the running status of the drive
Runs/
Ready
R
Binary Value
#1 (BV1)
Fwd/Rev
Status
Indicates the rotation direction of the drive Rev/Fwd R
Binary Value
#2 (BV2)
Fault Status Indicates the fault status of the drive
Faulted/
None
R
Binary Value
#4 (BV4)
Local/Remote
Status
Indicates if the drive is being locally
controlled
Local/
Remote
R
Binary Value
#6 (BV6)
Maint Req
Indicates if the cumulative run timer has
expired
Yes/No R