3
•Donotuseanyrefrigerantdierentfromtheonespeciedforcomplementor
replacement.
Otherwise,abnormallyhighpressuremaybegeneratedintherefrigeration
cycle,whichmayresultinafailureorexplosionoftheproductoraninjuryto
your body.
•Donotusemeanstoacceleratethedefrostingprocessortoclean,otherthan
those recommended by the manufacturer.
• The appliance shall be stored in a room without continuously operating ignition
sources(forexample:openames,anoperatinggasapplianceoranoperating
electric heater).
• Be aware that refrigerants may not contain an odour.
•Donotpierceorburnastheapplianceispressurized.Donotexposethe
appliancetoheat,ame,sparks,orothersourcesorignition.
Else,itmayexplodeandcauseinjuryordeath.
•ForR32model,usepipes,arenutandtoolswhichisspeciedforR32
refrigerant.Usingofexisting(R22)piping,arenutandtoolsmaycause
abnormallyhighpressureintherefrigerantcycle(piping),andpossiblyresultin
explosionandinjury.
• Thickness of copper pipes used R32 must be more than 0.8 mm.
Never use copper pipes thinner than 0.8 mm.
•Aftercompletionofinstallationorservice,conrmthereisnoleakageof
refrigerantgas.Itmaygeneratetoxicgaswhentherefrigerantcontactswithre.
• Comply with national gas regulations.
• After installation work, make sure below before operation.
- Connection pipes are connected properly and no leakage.
- Packed valves are fully open.
Running compressor without open packed valves may cause abnormal high
pressure and parts failure.
Leakage at connection piping may suck air and make further high pressure
causeburstandinjure.
• During pump down work make sure below process.
- Don’t mix air into the refrigerant cycle.
- Stop the compressor before removing piping after packed valves are
fully closed.
Removingpipingunderthecompressorrunningandpackedvalvesopen,
airmightbesuckedandrefrigerationcyclepressurebecomesabnormallyhigh,
anditcausesburstorinjuryonpersons.
EN