– 18 –
FILE NO. SVM-10017
6. SPECIFICATION OF ELECTRICAL PARTS
6-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) AFN-220-20-4D AC Motor with 145°C thermo fuse
2 Thermo. sensor (TA-sensor) 10 kΩ at 25°C
3 Switching transformer (T01) ST-02
4 Microcontroller unit (IC81)
5 Heat exchanger sensor
10 kΩ at 25°C
(TC-sensor)
6 Line filter (L01) SS11V-R06270 27 m H, AC 0.6A
7 Bridge diode (DB01) DB105G 1A, 600V
8 Capacitor (C27)
9 Fuse (F01) FJL250V3.15A 3.15A, 250 V
10 Regulator IC (IC02) S7805PIC 5VDC, 0.5A
11 Varistor (R01) SR561K14DO 560V
12 Louver motor
EKMH401VSN470MP20S 47µF, 400V
µPD780076GK-703-9ET-A
24BYJ48 DC 12V
6-2. Outdoor Unit
No. Parts name Model name Rating
1 SC coil L01 GET-04051 0.6mH, 15A
(Noise filter) L03 GET-04052 10A, 2mH
Primary side DC280V, Secondary
2 DC-DC transformer
SWT-72
side 7.0 V x 1, 12 V x 1, 17V x 2
3 Reactor CH-69-Z-T L=19mH, 10A
4 Outside fan motor
WLF-240-20A-1
20W
5
G5NB-1A-CA Coil DC12V Contact 3A/125VAC
6
Outside air temp.
(Inverter attached) 10kΩ (25°C)
sensor (TO sensor)
8
JX0-5B
20A, AC250V
Terminal block (5P)
9
11
Fuse
For protection of switching power source 3.15A, AC250V
For protection of inverter input overcurrent 25A, AC250V
12
Electrolytic capacitor
LLQ2G501KHUATF
500µF, DC 400 V x 3 pieces
13
Rectifier
Fan control relay
D15XB60-4001 15A, 600V
IGBT
GT15J321
15A, 600V
Compressor DA89X1C-23EZ 3-phases 4-poles 750W
14
9
Dischenge temp.
(Inverter attached)
10kΩ (25°C)
sensor (TD sensor)
15 Running capacitor
DS451155NPQB
AC 450V~, 1.5µF
(for fan motor)
16
4-WAY valve coil
STF-01AJ646A1 AC 220-240V
Heat exchanger temp.
(Inverter attached)
62kΩ (20°C)
sensor (TE sensor)
7