27
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 3 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
Description
* Symbols
UH : Ultra High
H : High
M+ : Medium+
M : Medium
L+ : Low+
L: Low
L- : Low
UL : Ultra Low
SUL : Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
M or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[
˚C
]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + L) x 3/4 + L
*4 : Fan speed = (M + L) x 2/4 + L
*5 : Fan speed = (M + L) x 1/4 + L
(Linear approximation
from M+ and L)
FILE NO. SVM-10017
L
W6
Indication
Fan speed
M
W9
H
WC
Fan speed
level
COOL HEAT DRY
WF UH
WE H
WD UH M+
WC H
WB M+
WA
W9 M L+
W8 L
W7
L+
L-
L+
W6
L
L
W5 L- UL L-
W4 UL UL
W3 SUL SUL
W2 SUL
W1
UH
H
M
M+
M
Fan
speed Air flow rate
(rpm) (m3/h)
1350 607
1300 576
1250 554
1200 522
1120 486
1100
1040 444
960 402
910 376
880 360
830 334
800 318
700 266
650 239
600 213
468