Tempeature Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 0.9 to 1.1 9 to 11 47 to 49 High High 54
<Heating>
Tempeature Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 2.4 to 2.6 43 to 45 0 to 3 High High 68
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition 5 m
– 20 –