11-3-13.TE Sensor (Outdoor
Heat Exchanger
Temperature Sensor)
Attachment
1) Install the TE sensor onto the straight part of
the condenser output pipe with the lead wires
pointing upward and the sensor facing the rear
of the cabinet.
11-3-14.TS Sensor (Suction
Temperature Sensor)
Attachment
1) Install the TS sensor onto the straight part of
the suction pipe with the lead wires pointing
upward and the sensor facing the packed
valve.
11-3-15.TD Sensor (Discharge
Temperature Sensor)
Attachment
1) Install the TD sensor onto the straight part of
the discharge pipe with the lead wires pointing
upward and the sensor facing the front of the
cabinet.
11-3-16.TO Sensor (Outside Air
Temperature Sensor)
Attachment
1) Install the TO sensor at the upper part of the
heat exchanger with the left edge aligned with
the heat exchanger edge panel.
CAUTION
During (and at the end of) the installation work, take
care not to damage the coverings of the sensor leads
on the edges of the metal plates or other parts.
Damaged lead coverings may cause electric shock or
fire.
After sensors have been replaced, check whether
each sensor is installed properly at the specified
position. Incorrect or improper installation will not
ensure correct control of the product, which may result
in a failure.
Detail A
(TE)
Detail B
(TS)
Detail C
(TD)
Detail D
(TO)
Detail A
Detail B
Detail C
Detail D