Toshiba
6-2. Operation Data
Cooling
Heating
NOTE
Measure surface temperature of heat exchanger pipe around centre of heat exchanger path U bent.
(Thermistor thermometer)
Connecting piping condition : 5 m
Temperature
condition (°C)
Model name
RAS-
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
Indoor
fan mode
Outdoor
fan mode
Compressor
revolution
(rps)
Indoor Outdoor T1 (°C) T2 (°C)
27/19 35/–
07PKVP-E
07PKVP-ND
1.0 to 1.2 14 to 16 39 to 42 High High 26
10PKVP-E
10PKVP-ND
1.0 to 1.2 13 to 15 40 to 43 High High 34
10PKVP-E
10PKVP-ND
0.9 to 1.1 10 to 13 42 to 45 High High 54
16PKVP-E
16PKVP-ND
0.8 to 1.0 8 to 11 44 to 47 High High 77
18PKVP-E
18PKVP-ND
0.8 to 1.0 7 to 10 45 to 48 High High 90
Temperature
condition (°C)
Model name
RAS-
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
Indoor
fan mode
Outdoor
fan mode
Compressor
revolution
(rps)
Indoor Outdoor T1 (°C) T2 (°C)
20/– 7/6
07PKVP-E
07PKVP-ND
1.8 to 2.0 32 to 34 2 to 4 High High 35
10PKVP-E
10PKVP-ND
2.0 to 2.2 35 to 37 2 to 4 High High 45
13PKVP-E
13PKVP-ND
2.2 to 2.4 38 to 41 2 to 4 High High 60
16PKVP-E
16PKVP-ND
2.5 to 2.7 43 to 46 1 to 3 High High 85
18PKVP-E
18PKVP-ND
2.6 to 2.8 44 to 47 1 to 3 High High 93
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 28 Wednesday, March 4, 2009 11:22 AM