High Wall, Heat Pump Type
Service Manual
49
Toshiba
5) Push the button of the remote controller that
was set in step 1 to stop the air conditioner.
(This operation will change the setting to “B”.)
6) Check that the remote controller operates the
indoor unit.
8-17.Set Temperature
Correction
8-17-1.Purpose
When the difference between the set temp. of the
remote controller and the room temp. is wide due to the
installation condition, etc, the set temp. is corrected.
(HEAT operation only)
8-17-2.Description
The set temp. received from the remote controller is
corrected. The correct value from –2°C to +4°C is
changed by the jumper wire on P.C. board of the indoor
microcomputer.
Indoor Control P.C. Board (Factory Default)
In HEAT Operation
In 8°C HEAT Operation (-ND model only)
L01
DB01
C03
T101
IC801
J804
J805
J806
J807
Jumper wire
J804
J805
J806
J807
At shipment
: With Jumper wire
×
: Cut Jumper wire
Jumper wire setup
J804 J805
××
×
×
HEAT
shift value
–2
+4
+2
0
At shipment
Jumper wire setup
J806 J807
××
×
×
HEAT
shift value
–2
+4
+2
0