High Wall, Heat Pump Type
Service Manual
19
Toshiba
NOTE
Be sure to make setting so that liquid can be
charged.
When using a cylinder equipped with a siphon,
liquid can be charged without turning it upside
down.
It is necessary for charging refrigerant under condition
of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the
refrigerant cylinder to the equipment, charge it turning
the cylinder upside down if cylinder is not equipped
with siphon.
Fig. 2-4-2
Cylinder with siphon
Fig. 2-4-3
Cylinder without siphon
NOTE
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of
the charged refrigerant changes and the
characteristics of the equipment varies.
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Siphon
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance