– 29 –
TA (°C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
–0.5
HH
(HH)
H+ (HH)
H (HH)
L+ (H+)
L (H)
L (H)
L (L+)
D
C
B
A
E
F
G
TA (°C)
(+0.5) +1.0
(0) Tsh
(-0.5) -1.0
(-1.0) -2.0
(-1.5) -3.0
(-2.0) -4.0
L (L+)
L+ (H)
H (H+)
HH
(HH)
H+
(HH)
E
D
C
B
A
No.
6
Item
Fan speed
selection
Outline of specifications
1) Operation with (HH), (H+), (H), (L+) (L) or [AUTO] mode
is carried out by the command from the remote controller.
2) When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between TA and Ts.
<COOL>
Controlling operation in case when thermostat of remote
controller works is same as a case when thermostat of the
body works.
Once the fan speed changes, it doesn't change for 3
minutes. However, you can change the fan speed using
the remote controller.
When cooling operation has started, select a downward
slope for the fan speed, that is, the high position.
If the temperature is just on the difference boundary, the
fan speed does not change.
Mode in the parentheses indicates one in automatic
cooling operation.
<HEAT>
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat of
the body works.
Once the fan speed changes, it doesn't change for 3
minutes. However, you can change the fan speed using
the remote controller.
When heating operation has started, select an upward
slope for the fan speed, that is, the high position.
If the temperature is just on the difference boundary, the
fan speed does not change.
Mode in the parentheses indicates one in automatic
heating operation.
In TC 60°C, the fan speed increases by 1 step.
Remarks
HH > H+ > H > L+ >
L > UL
TC: Indoor heat
exchanger sensor
temperature