E6582051
- 43 -
6.5.12.
fd01
(Inverter operating status 1 (real time)) (VF-S15)
bit
Function
0
1
Note
0
Failure FL
No output
Under in progress
-
1 Failure Not tripped Tripped
Trip status includes
rtry
and
the trip retention status are also
regarded as tripped statuses.
2
Alarm
No alarm
Alarm issued
-
3
Under voltage (
moff
)
Normal
Under voltage
-
4
Motor selection (1 or 2)
(THR 2 selection)
Motor 1 (THR1) Motor 2 (THR2)
THR1:
pt
= setting value,
vl
,
vlv
,
vb
,
thr
THR2:
pt
=
0
,
f170
,
f171
,
f172
,
f173
5 PID control off
PID control
permitted
PID control
prohibits
-
6
Acceleration/deceleratio
n pattern selection (1 or
2)
Acceleration/dec
eleration pattern
1 (AD1)
Acceleration/dec
eleration pattern
2 (AD2)
AD1:
acc
,
dec
AD2:
f500
,
f501
7 DC braking OFF
Forced DC
braking
-
8
Jog run
OFF
Jog run
-
9
Forward / reverse run
Forward run
Reverse run
-
10
Run/stop
Stop
Run
-
11
Coast stop (ST = OFF)
ST=ON
ST=OFF
-
12 Emergency stop
No emergency
stop status
Emergency
stop status
-
13 Standby ST=ON Start-up process Standby
Standby: Initialization
completed, not failure stop
status, not alarm stop status
(
moff
,
ll
forced stop),
ST=ON, and RUN=ON
14 Standby Start-up process Standby
Standby: Initialization completed,
not failure stop status and not
alarm stop status (
moff
,
ll
forced stop)
15
(Undefined)
-
-
-
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgment.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)