Table 28. 27.5 - 35 Ton horizontal economizer (O/A) - ultra-low-leak economizer (continued)
System
Design CFM
Return Air Duct Static + Return Air Damper Static (Inches of Water)
0.2 0.4 0.6 0.8 1 1.2 1.4
Stroke limit setting % on OA damper actuator
9500 100 50 45 40 40 40 40
10000 100 60 50 40 40 40 40
11000 100 60 50 45 40 40 40
11500 100 80 50 45 40 40 40
12000 100 100 60 45 40 40 40
12500 100 100 60 50 45 40 40
13000 100 100 60 50 45 40 40
13500 100 100 70 50 45 45 40
14000 100 100 70 60 50 45 40
14500 100 100 80 60 50 45 45
15000 100 100 80 60 50 45 45
15500 100 100 80 60 50 50 45
Table 29. 40 - 50 Ton downflow economizer (O/A) - ultra-low-leak economizer
System
Design CFM
Return Air Duct Static + Return Air Damper Static (Inches of Water)
0.2 0.4 0.6 0.8 1 1.2 1.4
Stroke limit setting % on OA damper actuator
12000 100 100 65 60 55 55 55
12500 100 100 65 60 60 55 55
13000 100 100 75 65 60 55 55
13500 100 100 75 65 60 60 55
14000 100 100 75 65 65 60 55
14500 100 100 75 75 65 60 60
15000 100 100 100 75 65 60 60
15500 100 100 100 75 65 60 60
16000 100 100 100 75 65 65 60
16500 100 100 100 75 75 65 60
17000 100 100 100 75 75 65 65
17500 100 100 100 100 75 65 65
18000 100 100 100 100 75 65 65
18500 100 100 100 100 75 75 65
19000 100 100 100 100 75 75 65
19500 100 100 100 100 75 75 75
20000 100 100 100 100 100 75 75
20500 100 100 100 100 100 75 75
21000 100 100 100 100 100 75 75
21500 100 100 100 100 100 100 75
22000 100 100 100 100 100 100 80
Startup