16. Control logic description
66 SS-SVM001A-EM
16.5 Condenser High-temperature Protection
DC-Inverter outdoor unit
AC will enter T3 protection if any of the following conditions is satisfied.
Cooling mode: When the saturation temperature (which is got from low pressure cycling) T2
keeps lower than TE5 for 120 seconds, the compressor and outdoor fan will shut off. When T2 is
higher than TE6, the compressor and outdoor fan will restart up.