Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Cooling mode
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
10 15 20 25 30 35 40
Ambient temperature (°C)
Return air mix temperature (°C)
Operating map at cooling mode
Operating map of cooling mode
Low ambient
Low ambient
Standard ambient
Minimum Outdoor Temperature = -15 °C
Maximum Indoor Coil Mixed Temperature = 35°C
Minimum Indoor Coil Mixed Temperature = 5 °C
Heating mode
-20
-15
-10
-5
0
5
10
15
20
25
0 5 10 15 20 25 30
Ambient temperature (°C)
Return air mix temperature (°C)
Operating map at heating mode
Operating map of heating mode
Minimum Outdoor Temperature = -15°C
Maximum Indoor Coil Mixed Temperature = 27°C
Minimum indoor Coil Mixed Temperature = 5°C
Operating Map