RT-SVX060A-GB
34
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Free cooling economizer unit is supplied with
economizer and fresh air hood as a standard feature.
Fresh air percentage can vary from 0 to 100%.
An economizer consists of:
• A motorized damper with separate fresh air and return
air sections.
• A fresh air hood with a grill delivered folded in the
unit.
• All necessary sensors for free cooling operation.
The mechanical opening of the damper is managed by
the actuator which is adjusted by Trane controller.
Damper is activated in free cooling mode and may be
further controlled by temperature control with return
and outdoor air sensors or by enthalpy control with
addition to temperature sensor of return and outdoor
humidity sensor.
Fresh air hood installation
Figure 13 - Fresh air hood assembly steps
Horizontal Flow
Step 1: Remove
sheet metal hood
Step 2: Position
the flange with
corner on the
outside
Step 3: position
the cover hood
Step 4: Repeat
the steps 2 and 3
Step 5: Repeat
the steps 2 and 3
Down Flow
Step 1: Remove
sheet metal hood
Step 2: Position
side flange
with corner on
the outside
Step 3: position
the cover hood
Building Pressurization Control
Barometric Relief
The barometric relief allows to minimize overpressure
in the building caused by the introduction of fresh air.
This option is typically installed when fresh air intake is
below 25% of the nominal air flow and when the return
air pressure drop is below 25Pa.
Barometric damper is integrated as standard into
economizer option on downflow and not compatible
with heat recovery module unit only.
When the pressure of the building increase, the
dampers open and relieve air to the outside.
If the return air duct pressure drop is higher than the
building overpressure, the dampers will not open.
If the return air duct pressure drop is lower than the
building overpressure, the dampers will open and
relieve air outside of the building.
Figure 14 - Barometric relief
Options