RT-SVX060A-GB
7
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Unit Model Number Description
Digit 30 - Literature Language
B = Spanish
C = German
D = English
E = French
J = Italian
P = Polish
V = Portuguese
Digit 31 - Building Pressurization Control
X = Without
1 = Barometric relief damper
B = Configured for Rotary wheel high airflow
U = Energy Recovery Circuit EC fans
4 = Configured for return roofcurb (ESP = 250Pa)
Digit 32 - not used
Digit 33 - External Customer Input/Output
X = Without
1 = With
Digit 34 - Multi-Rooftop Control
X = Without
C = With Tracer Concierge Comfort
T = With Tracer Concierge comfort with Display
(Recommended)
Digit 35 - Communication interfrace
X = Without
1 = ModBus communication interface
2 = LonTalk® communications interface
3 = BACnet (MSTP)
Digit 36 - Not used
Digit 37 - Compressor Starter Type
X = Across the line
A = Soft starter
Digit 38 - Service User Interface
X = Without
1 = Service terminal PGD (supplied loose)
Digit 39 - Fire Thermostat
X = Without
1 = With
Digit 40/41/42/43 - Not used
Digit 44 - Condenser Guard grill
X = Without
A = With condenser guard grill
Digit 45 - Export Packaging
X = Without
A = With export packaging
Digit 46 - Special design
X = Standard