Installation - Mechanical
26 CLCH-SVX010A-EN
Base-to-Interior Wall
Note: Corner gussets are to ensure unit squareness
during shipping, lifting, and assembly. Please
remove, when unit is set in place.
Note: Failure to completely compress the gasketing may
result in air leakage.
1. Join the two units and secure with field provided 5/8-
inch flat washers and 5/8-inch X 2-1/2-inch grade 9 bolts
though each of the six holes.
2. Apply caulk the length of the base between the 2-inch
X 2-inch angle on the one base section and the wall on
the adjoining section.
Note: Note: Use a polyurethane or equivalent caulk.
3. Secure the 2-inch X 2-inch angle to the adjoining wall
with #14 sheet-metal crews on 12-inch centers along
the length of the angle and wall.
Figure 26. Base-to-interior wall sections
Interior
wall
4-in. x 1/4-in. gasket
In lieu of joining strip, secure
2-in. x 2-in. angle to wall with
#14 SM screws at 12-in. centers
Caulk
Split
Split
Interior
wall
Caulk
Caulk
Split
Split
Base-to-Wall Assembly Complete