Routine Maintenance
CLCH-SVX010A-EN 77
Fans
Inspecting and Cleaning Fans
Fan sections of air handlers should be inspected every six
months at a minimum or more frequently if operating
experience dictates. If evidence of microbial growth
(mold) is found, identify and remedy the cause
immediately. Refer to “Troubleshooting,” p. 81 for
possible causes and solutions. To clean the fan section:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate personal protective
equipment, remove any contamination.
3. Vacuum the section with a vacuum device that uses
high-efficiency particulate arrestance (HEPA) filters
with a minimum efficiency of 99.97 percent at
0.3 micron particle size.
4. Thoroughly clean any contaminated area(s) with a
mild bleach and water solution or an EPA-approved
sanitizer specifically designed for HVAC use.
5. Immediately rinse the affected surfaces thoroughly
with fresh water and a fresh sponge to prevent
potential corrosion of metal surfaces.
6. Allow the unit to dry completely before putting it back
into service.
7. Be careful any contaminated material does not contact
other areas of the unit or building. Properly dispose of
all contaminated materials and cleaning solution.
Bearing Set Screw Alignment
Align bearing set screws for belt-drive fans. See Table 2,
p. 56 for set screw torque measurements.
Torque Requirements
Refer to Tab le 8 for minimum torque of motor mounting
and bearings bolts. Refer to Table 2, p. 56 for minimum
setscrew torque.
Fan Bearing Lubrication
For belt-drive fans, the grease used in electric motor
bearings is usually not compatible with the grease used in
fan bearings. Never mix the two grease types! See Tab le 9
for compatible greases and Ta ble 10 for maximum grease
capacity.
WARNING
Rotating Components!
The following procedure involves working with rotating
components. Disconnect all electric power, including
remote disconnects before servicing. Follow proper
lockout/ tagout procedures to ensure the power can
not be inadvertently energized. Secure rotor to ensure
rotor cannot freewheel. Failure to secure rotor or
disconnect power before servicing could result in
rotating components cutting and slashing technician
which could result in death or serious injury.
Figure 94. Alignment
Table 8. Minimum hex head bolt torque in lb.-ft.
(Grade 5 bolts)
Size (inches) Thread Designation Minimum Torque
1/4-20 UNC 6
1/4-28 UNF 7
65/16-18 UNC 14
5/16-24 UNF 16
3/8-16 UNC 24
3/8-24 UNF 28
7/16-14 UNC 42
7/16-20 UNF 45
1/2-13 UNC 69
1/2-20 UNF 83
9/16-12 UNC 99
9/16-18 UNF 118
5/8-11 UNC 150
5/8-18 UNF 176
3/4-10 UNC 254
3/4-16 UNF 301
7/8-9 UNC 358
7/8-14 UNF 422
1-8 UNC 500
1-14 UNF 602
Note: Soft metric conversions are not acceptable for screw and hex sizes.
NOTICE:
Bearing Failure!
Do not mix greases with different bases within the
bearing. Mixing grease within the bearing could result
in premature bearing failure.
Align set screws
Align set screws