WSHP-SVX022A-EN
31
Table 6. Console VA
Designator
Controls
Deluxe with
Reheat (75 VA)
Deluxe with Electric
Heat (75 VA)
Symbio™ 400-B (75
VA)
x = ON
(a)
Controller 6.0 6.0 12.5
1K1
Compressor Contactor
5.5 5.5 5.5 X
1K2
Fan Relay
9.5 9.5 9.5
2L1
Reversing Valve
5.0 5.0 5.0 X
2L2 Reheat Valve 5.0 — —
5B3
Damper Actuator
— — —
1K10 Electric Heat Contactor — 5.5
Optional
(b)
X
IU3 Boilerless Control Board — 3.0 N/A X
Field Supplied Solenoid
7.0 7.0 7.0 X
1K6, 1K7
Reheat Relays(2)
12.5 —
Optional
(c)
X
1K8
Reheat Low Speed Relay
— — N/A X
1U1 Thermostat-Unit Mounted 6.0 6.0 N/A X
Timer Delay Relay
N/A N/A N/A X
Total VA 56.5 47.5 39.5 61.40
Extra VA 18.5 27.5 32.5 13.60
Note: Listed VA values are for reference only. Actual values may vary with operating conditions.
(a)
Consider unit options and concurrent loads.
(b)
Electric heat is optional with Symbio™ 400-B controller. If electric heat is selected, add 5.5 VA.
(c)
HGR is optional with the Symbio™ 400-B controller. If HGR is selected, add 12.5 VA.
Electrical Data