WSHP-SVX022A-EN
7
Operating Limits
Table 1. Operating limits
Operating Limits Cooling Heating
Air Limits
Min. ambient air DB
45°F (7°C)
Max. ambient air DB
130°F (54.4°C)
Min. EAT DB/WB
65.6/49.4°F (18.7/9.7°C) 53.0°F/- (11.7°C/-)
Max. EAT DB/WB
85.6/77.1°F (29.8/25.1°C) 83.0°F/- (28.3°C/-)
Airflow range
307 to 580 CFM/ton
(a)
Water Limits
Min. entering water temperature 45°F (7°C) 25°F (-4°C)
Max. entering water temperature 120°F (49°C) 86°F (30°C)
Max. water pressure 400 PSIG (2758 kPa)
Water flow range
1.8 to 4.0 GPM/ton
(a)
(a)
See performance tables for each model's rated values.