26
System Programming SETUP
Used on Units:
All Units
Possible Values:
30 to 600 seconds
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
30 to 255 seconds
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Enable, Disable
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
None - No Reset Applied
Outside Air Temp Reset
1. Press the + or - key until the proper value is displayed. Zone Temp Reset
2. Press the ENTER key to confirm this choice. Enterin
Solution Temp Reset
3. Press the NEXT key until the following screen is displayed.
The followin
two screens will display when either OA, Zone, or
ENT Soln Reset is selected.
1. Press the + or - key until the proper value is displayed.
Used on Units:
All Units with Leaving Solution Reset
2. Press the ENTER key to confirm this choice.
Possible Values:
3. Press the NEXT key to advance the cursor to the "End Temp" Reset Type: Outside Air Temp Reset
4. Press the + or - key until the proper value is displayed. Zone Temp Reset
5. Press the ENTER key to confirm this choice. Enterin
Soln Temp Reset
6. Press the NEXT key until the followin
screen is displayed.
Start Temp OA: 46 - 125 F
ENT Soln Temp Reset: 6 - 80 F
End Temp OA: 45 - 124 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. ENT Soln Temp Reset: 5 - 79 F
3. Press the NEXT key until the followin
screen is displayed. Max Amount (Zone, OA, ENT Soln Temp Reset): 3 - 16 F
1. Press the + or - key until the proper value is displayed.
Used on Units:
All Units
2. Press the ENTER key to confirm this choice.
Possible Values:
Comfort Coolin
, Process Coolin
3. Press the NEXT key until the followin
screen is displayed.
Evap Soln Pump Off Delay time 30 Sec
Delay Pump OFF Request By This Amount
Loop Stabilization Time: 120 Sec
Run Pump To Allow Soln Temp To Stabilize
Low Ambient Compressor Lockout: ENABLED
Use Low Ambient Compressor Lockout STP
Leaving Solution Reset Type:
NONE - NO RESET APPLIED
Select Type of Cooling Control Based On
Chiller Application: PROCESS COOLING
Reset Type: Outside Air Temp Reset
Start Temp 70.0 F End Temp 50.0 F
Reset Type: Outside Air Temp Reset
Maximum Amount of Reset A
lied 5.0 F