EasyManua.ls Logo

Trane IntelliPak CGAF Series - CGM Ice Build Relay Output; GBAS 0-10 VDC Module Relay Output; CGM ICS Controlled Relay

Trane IntelliPak CGAF Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
System Testing & Troubleshooting
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With Ice Building Control Option
Possible Values:
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With GBAS 5VDC Module Option
Possible Values:
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Repeat steps 1 - 4 for Outputs 3, 4 & 5.
7. Press the NEXT key until the following screen is displayed.
Used on Units:
With GBAS 10VDC Module Option
Possible Values:
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With GBAS 10VDC Module Option
Possible Values:
0.0 to 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "#2 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
Used on Units:
With GBAS 10VDC Module Option
Possible Values:
0.0 to 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor to the "#4 Output"
4. Press the + or - key until the proper value is displayed.
5. Press the ENTER key to confirm this choice.
6. Press the NEXT key until the following screen is displayed.
Used on Units:
With TCI Module Option (For Future Use)
Possible Values:
On, Off
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
CGM Ice Build Relay Output : OFF
GBAS 0-5VDC Module Relay Outputs
#1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
GBAS 0-10VDC Module Relay Output: OFF
GBAS 0-10VDC Module Analog Outputs
Out #1 0.2 VDC Out #2 0.4 VDC
GBAS 0-10VDC Module Analog Outputs
Out #3 0.6 VDC Out #4 0.8 VDC
CGM ICS Controlled Relay: OFF

Table of Contents

Related product manuals