System Programming SETPOINTS
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With Ice Building Control Option
Possible Values:
Human Interface STP Menu
GBAS 0-5VDC Module
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Human Interface STP Menu
GBAS 0-5VDC Module
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With GBAS5V or GBAS10V
Possible Values:
No Source Selected
GBAS 0-5VDC Module
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
3. Pressing the NEXT key will return to the 1st SETPOINT
screen.
4. Press the AUTO or STOP key to return to the top level
status information screen.
Use Ice Building Terminate Setpoint
From: HUMAN INTERFACE STP MENU
Use Hot Start Load Limit Setpoint
From: HUMAN INTERFACE STP MENU
Use Capacity Limit Setpoint
From: NO SOURCE SELECTED