35
SETPOINTS Menu
The SETPOINTS menu is used to designate default
setpoints, low ambient compressor lockout setpoints and
select setpoint sources.
These setpoints will be active (in use) for the "Setpoint
Source Selection" designated as "DEFAULT" for these in-
puts.
System Programming SETPOINTS
When a setpoint screen is displayed for 30 minutes without
a key being pressed, the LCD screen will revert to the gen-
eral operating status display. If this happens, press the
SETPOINT key again to return to the setpoint menu.
Used on Units:
All Units
Possible Values:
Based on Confi
ured Leavin
Solution STP Ran
e:
Ran
e 51.0 - 65.0°F
1. Press the + or - key until the proper value is displayed. Ran
e 40.0 - 50.0°F
2. Press the ENTER key to confirm this choice. Ran
e 30.0 - 39.0°F
3. Press the NEXT key until the followin
screen is displayed. Ran
e 20.0 - 29.0°F
Ran
e 10.0 - 75.0°F (SPECIAL)
Used on Units:
Units with Ice Buildin
Control Option
Possible Values:
20.0 to 31.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
All Units
Possible Values:
-10.0 to 60.0 F
Note: Maximum settin
may be limited by āHi Leavin
1. Press the + or - key until the proper value is displayed. Solution Setpointā
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
Possible Values:
0 to 45.0 F
Note: Maximum settin
may be limited by āHi Leavin
1. Press the + or - key until the proper value is displayed. Solution Setpointā
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
All Units
Possible Values:
60.0 to 80.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
All Units
Possible Values:
-20.0 to 50.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
All Units
Possible Values:
-20.0 to 60.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the followin
screen is displayed.
Used on Units:
All Units
Possible Values:
Human Interface STP Menu
GBAS 0-5VDC Module
1. Press the + or - key until the proper value is displayed. GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice. Ext Leavin
Soln STP Input
Stop Ice Making When Ent Soln Temp Below
Hi Ice Build Terminate Set
oint: 27.0 F
Comp(s) OFF if Solution Temp Below
Low Solution Cutout Tem
: 35.0 F
HI Hot Start Load Limit Setpoint: 71.0 F
Request Pump ON When OA Temp Less Than
Low Ambient Pum
Override Tem
: 35 F
Low Ambient Comp Lockout Temp: 40 F
Com
s
OFF if OA Tem
Below This Value
Use Leaving Solution Setpoint
From: HUMAN INTERFACE STP MENU
Heat Output ON When EST or LST Less Than
Heat Ta
e Tem
erature Set
oint: 40.0 F
HI Leaving Solution Setpoint: 44 F