System Testing & Troubleshooting
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
The CGM has lost communications
with the GBAS Module.
The UCM will initiate the following
actions;
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints.
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
module will cause all GBAS
outputs to be zeroed and
de-ener
g
ized.
(PAR) An automatic reset occurs
after communication has been
restored.
GBAS 0-5VDC Module Comm
Failure
Problem: The CGM has lost
communications with the GBAS
Module.
Check: Check field/unit wiring
between CGM and GBAS.
The CGM has lost communications
with the GBAS Module.
The UCM will initiate the following
actions;
a. If the Demand Limit input was
closed prior to communications
loss, then the Demand Limit
commands issued to the
Compressor Staging function
will be cancelled.
b. If any of the GBAS setpoint
control parameters are the
HI-selected setpoint sources,
then those setpoints will revert
to the default HI setpoints.
c. Any active GBAS output
control parameters will be
ignored.
d. A failsafe function in the GBAS
module will cause all GBAS
outputs to be zeroed and
de-ener
g
ized.
(PAR) An automatic reset occurs
after communication has been
restored.