System Testing & Troubleshooting
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
Liquid Pressure Sensor Fail Circuit 2
(Circuit #2 40-60 Ton units only)
Problem: Circuit 2 Saturated Liquid
Line Pressure sensor input is out of
range.
Check: Check field/unit wiring
between Sensor and SSM.
The unit is reading a signal that is out
of range for the Circuit 2 Saturated
Liquid Line Pressure Sensor input on
the SSM. (Pressure < 0 PSIG or
Pressure > 400 PSIG).
The Superheat/Subcool
calculation is invalid and the
vaiues are set to zero. No other
change in unit operation occurs.
This dia
g
nostic is for information
only.
(INFO) An automatic reset occurs
after the Circuit 2 Saturated Liquid
Pressure Sensor input returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic, there
is a 10 second delay before the
automatic reset.
Low Ambient Evaporator Solution
Pump Override
Problem: Outside Air Temp too low,
reques t Solution Pum p to run to
keep Solution moving.
The Outside Air (Ambient)
temperature is below the Low
Ambient Evap Pump Override Temp
Setpoint.
The Evaporator Solution Pump
Relay is energized while this
condition exists.
(PAR) An automatic reset occurs
after the Outs ide Air Tem p
increases 5 deg F or more above
the Low Ambient Evaporator Pump
Override Temp Setpoint.
Low Solution Cutout Temperature
(Auto)
Problem: The Evaporator Leaving or
Enterin
g
Solution Temperature is too
low.
While no compressors were running,
the Evaporator Solution
Temperature(s) went below the Low
Solution Cutout Tem p Setpoint.
While this diagnostic is active,
Compressors are prevented
from staging on. The Unit will
deenergize the following:
Compressor Relays, LPC
Bypass Relays, Liquid Line
Solenoids, and HGBP Relay.
(PAR) An automatic reset occurs
after the Evaporator Solution
Temperature(s) rises 4 deg F or
more above the Low Solution Cutout
Temperature Setpoint.
Low Solution Cutout Temperature
(Man)
Problem: The Evaporator Leaving or
Enterin
g
Solution Temperature is too
low.
While compressors were runnin
g
, the
Evaporator Solution Temperature(s)
went below the Low Solution Cutout
Temperature Setpoint.
A "Lockout all Circuits" request is
issued to the Compressor
Staging Function. Compressors
are prevented from staging on
and the Unit will de-energize the
following relays: Compressor
Relays, LPC Bypass Relays,
Liquid Line Solenoids, and
HGBP Relay.
(PMR) A manual reset is required
after this diagnostic occurs. The
Diagnostic can be reset by the unit
mounted Human Interface Module
or Tracer, or by cycling power to the
CGM.
Low Pressure Control Open -
Circuit 1
Problem: The refrigerant in Circuit 1
is cold and may cause the Solution
in the Chiller barrel to become too
cold. Also, there may be a state of
charge issue with Circuit 1.
With one or more compressors
running, the higher pressure of the
two LPC switches on Circuit 1 has
opened 6 times with the LPC Bypass
relay de-energized, or it was open at
the time the LPC Bypass Relay de-
energized. On a standard unit this is
the 45 PSIG LPC switch, but can be
20 PSIG or lower on units with a lower
Leaving Solution Setpoint range.
A “Lockout Circuit # 1” request is
issued to the Compressor
Staging Control function. The
Compressor Relays, LPC
Bypass Relay, Liquid Line
Solenoid Relay, and Hot Gas
Bypass Relay for Circuit 1 are all
de-energized.
(PMR) A manual reset is required
anytime after the Diagnostic is set.
The Diagnostic can be reset by the
Human Interface or Tracer, or by
cycling power to the CGM.